Expansion modules

Adquio Multi IOs

Gather inputs and outputs in an expansion module connected by Modbus RTU. Adapt signal acquisition and control commands to each zone of the facility.

Adquio Multi IOs

INPUTS, OUTPUTS AND MACHINE CONTROL

Bring your machine signals together in a single module

Connect sensors, PT1000 probes, relays and analogue and digital signals for exchangers, chillers, evaporator and condenser units, air handling units and other equipment.

Adquio Multi IOs combine inputs and outputs with Modbus RTU communication to simplify machine integration and centralise your signals.

Adquio Multi IOs
8AI / DI
4PT1000
5Relays
4DO · 24 V
4AO · 0–10 V
2RS-485

As expansion module

Connect the RS-485 slave port to an Adquio controller or another compatible Modbus RTU master. The controller collects the inputs and sends the orders to the outputs.

With machine-specific programming

For manufacturers and dedicated applications, custom programming allows the machine to be governed without an additional programmable controller. The master port allows you to incorporate a screen or a compatible thermostat to consult statuses, set setpoints and perform manual control. This mode requires specific study and programming.

Front connectors and top indicators

Front connectors and top indicators Adquio 18 Relay
  1. Power connection, 24V DC
  2. Micro switches for address configuration modbus.
  3. Slave 485 connector with 3 contacts A, B and GND. You use it to control this device from a adquio or higher controller.
  4. 485 master connector with 3 contacts A, B and GND. You use them if you want to connect a control display or thermostat directly to this device. (Designed for cases in which this device is used in a pre-programmed way to perform a very specific function, controlling a machine).
  5. 4 Inputs that can be used as analogue and digital, admit a voltage range from 0 to 24 volts, when read as digital, 1 is assumed when passing 4.7V.
  6. 4 pairs of contacts for 4 PT1000 probes.
  7. Error indicator.
  8. Correct connection indicator with the master.
  9. Power indicator

Rear connectors

Rear connectors Adquio 18 Relay
  1. 10 contacts for 5 dry contact relays with support up to 10A at 250V.
  2. 4 digital outputs 0-24V with power transistors to drive relays.
  3. 4 Inputs that can be used as analogue and digital, admit a voltage range from 0 to 24 volts, when read as digital, 1 is assumed when passing 4.7V.
  4. GND connector, ground or negative pole, useful for nearby digital outputs.
  5. 4 analogue outputs 0-10V.

Technical specifications

Power supply

Supply voltage24 V DC
Current130 mA
Maximum allowed voltage28 V DC
Peak start-up current150 mA

Connectivity

slave port1 · RS-485 · Modbus RTU
Master port1 · RS-485 · Modbus RTU
Communication speed9600–19200 bps
AddressDIP switches

Analogue and digital inputs

Configurable inputs8 · AI/DI
Analogue ranges0–10 V / 0–24 V
Logic level 1 digital> 4,7 V
Resolution12 bits
4–20 mA inputsRequires DIN rail converter

Sondas PT1000

Temperature inputs4 · PT1000
Resolution15 bits
AdjustmentSoftware-adjustable

Relay outputs

dry contacts5
Contact current10 A
Contact voltage250 V AC
DurabilityMore than 100,000 switching operations

Digital outputs

Outputs4 · 24 V · power transistors
Maximum load2 A

Analogue outputs

Outputs4 · 0–10 V
Resolution12 bits
Maximum load10 mA

Assembly and operating conditions

MountingHorizontal · DIN 35 mm
ProtectionIP20
Operating temperature0–60 °C
Storage and transportation−40–70 °C
Relative humidity≤ 95% no condensation
Status LED3 · Power, Online, Error

Certifications

Safety and healthEN ISO 13849-1: 2015
EN ISO 13849-2: 2012
EN 62061:2005 + A1:2013 + A2:2015
EN 60950-1:2006
EN 62311:2008
EMCEN 61000-6-4:2007 + A1:2011
EN 61000-6-2:2005
ETSI EN 301 489-1 v2.2.0
ETSI EN 301 489-17 v3.2.0
RoHSEN 50581: 2012

From the machine to its control platform

Measurements and statuses arrive at the controller; orders return to the outputs via Modbus RTU.

Field devices

Connect probes, sensors, relays and actuators to the corresponding inputs and outputs.

Adquio Multi IOs

Adquio Multi IOs

The module collects measurements and statuses and switches or regulates the connected outputs.

Adquio Mini

Adquio controller

Use a compatible Modbus RTU master, such as Adquio Mini, to coordinate logic, schedules and other building systems.

Adquio Analytics

Control and analysis

Use controller variables in control, monitoring, and historical data analysis interfaces.

Connect your project to the entire Adquio ecosystem.

Map sensors and actuators to Adquio Multi IOs inputs and outputs. We will help organise signals, variables and programming for the required function.