Configuration for Crompton* DRS-100-3P-MOD

DRS-100-3P-MOD

We continue adding the configuration of different devices that will help you to avoid having to do it manually, if you use this device you can copy and paste the configuration that we leave below. Thank you Eduardo from Impelsa for sharing your work with us.

{
"code": "DRS-100-3P-MOD_1",
"disabled": false,
"instance": "Puerto1_R485",
"modbusSlave": "1",
"name": "Analizer TE DRS-100-3P-MOD",
"pollInterval": 2000,
"schemaVersion": 5,
"type": "modbusrtu",
"variables": [
{
"canRead": true,
"canWrite": false,
"code": "REG001",
"dataType": "float32",
"modbusAddress": "0x0000",
"modbusRegType": "input_register",
"name": "Phase 1 line to neutral volts",
"type": "electric_power",
"units": "volts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG002",
"dataType": "float32",
"modbusAddress": "0x0002",
"modbusRegType": "input_register",
"name": "Phase 2 line to neutral volts",
"type": "electric_power",
"units": "volts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG003",
"dataType": "float32",
"description": "Phase 3 line to neutral volts.",
"modbusAddress": "0x0004",
"modbusRegType": "input_register",
"name": "Phase 3 line to neutral volts.",
"type": "electric_power",
"units": "volts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG004",
"dataType": "float32",
"description": "Phase 1 current.",
"modbusAddress": "0x0006",
"modbusRegType": "input_register",
"name": "Phase 1 current",
"type": "electric_power",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG005",
"dataType": "float32",
"description": "Phase 2 current",
"modbusAddress": "0x0008",
"modbusRegType": "input_register",
"name": "Phase 2 current",
"type": "electric_power",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG006",
"dataType": "float32",
"description": "Phase 3 current",
"modbusAddress": "0x000A",
"modbusRegType": "input_register",
"name": "Phase 3 current",
"type": "electric_power",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG007",
"dataType": "float32",
"description": "Phase 1 power.",
"modbusAddress": "0x000C",
"modbusRegType": "input_register",
"name": "Phase 1 power",
"type": "electric_power",
"units": "watts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG008",
"dataType": "float32",
"modbusAddress": "0x000E",
"modbusRegType": "input_register",
"name": "Phase 2 power",
"type": "electric_power",
"units": "watts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG009",
"dataType": "float32",
"modbusAddress": "0x0010",
"modbusRegType": "input_register",
"name": "Phase 3 power",
"type": "electric_power",
"units": "watts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG010",
"dataType": "float32",
"modbusAddress": "0x0012",
"modbusRegType": "input_register",
"name": "Phase 1 volt amps",
"type": "electric_power",
"units": "watts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG011",
"dataType": "float32",
"modbusAddress": "0x0014",
"modbusRegType": "input_register",
"name": "Phase 2 volt amps.",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG012",
"dataType": "float32",
"modbusAddress": "0x0016",
"modbusRegType": "input_register",
"name": "Phase 3 volt amps.",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG013",
"dataType": "float32",
"modbusAddress": "0x0018",
"modbusRegType": "input_register",
"name": "Phase 1 volt amps reactive",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG014",
"dataType": "float32",
"modbusAddress": "0x001A",
"modbusRegType": "input_register",
"name": "Phase 2 volt amps reactive",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG015",
"dataType": "float32",
"modbusAddress": "0x001C",
"modbusRegType": "input_register",
"name": "Phase 3 volt amps reactive",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG016",
"dataType": "float32",
"modbusAddress": "0x001E",
"modbusRegType": "input_register",
"name": "Phase 1 power factor",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG017",
"dataType": "float32",
"modbusAddress": "0x0020",
"modbusRegType": "input_register",
"name": "Phase 2 power factor",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG018",
"dataType": "float32",
"modbusAddress": "0x0022",
"modbusRegType": "input_register",
"name": "Phase 3 power factor",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG019",
"dataType": "float32",
"modbusAddress": "0x0024",
"modbusRegType": "input_register",
"name": "Phase 1 phase angle",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG020",
"dataType": "float32",
"modbusAddress": "0x0026",
"modbusRegType": "input_register",
"name": "Phase 2 phase angle",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG021",
"dataType": "float32",
"modbusAddress": "0x0028",
"modbusRegType": "input_register",
"name": "Phase 3 phase angle",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG022",
"dataType": "float32",
"modbusAddress": "0x002A",
"modbusRegType": "input_register",
"name": "Average line to neutral volts",
"type": "electric_power",
"units": "volts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG024",
"dataType": "float32",
"modbusAddress": "0x002E",
"modbusRegType": "input_register",
"name": "Average line current",
"type": "electric_power",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG025",
"dataType": "float32",
"modbusAddress": "0x0030",
"modbusRegType": "input_register",
"name": "Sum of line currents",
"type": "electric_power",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG027",
"dataType": "float32",
"modbusAddress": "0x0034",
"modbusRegType": "input_register",
"name": "Total system power",
"type": "electric_power",
"units": "watts"
},
{
"canRead": true,
"canWrite": false,
"code": "REG029",
"dataType": "float32",
"modbusAddress": "0x0038",
"modbusRegType": "input_register",
"name": "Total system volt amps",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG031",
"dataType": "float32",
"modbusAddress": "0x003C",
"modbusRegType": "input_register",
"name": "Total system VAr",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG032",
"dataType": "float32",
"modbusAddress": "0x003E",
"modbusRegType": "input_register",
"name": "Total system power factor",
"type": "electric_power",
"units": "no_units"
},
{
"canRead": true,
"canWrite": false,
"code": "REG034",
"dataType": "float32",
"modbusAddress": "0x0042",
"modbusRegType": "input_register",
"name": "Total system phase angle",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG036",
"dataType": "float32",
"modbusAddress": "0x0046",
"modbusRegType": "input_register",
"name": "Frequency of supply voltages",
"type": "electric_power",
"units": "hertzs"
},
{
"canRead": true,
"canWrite": false,
"code": "REG037",
"dataType": "float32",
"modbusAddress": "0x0048",
"modbusRegType": "input_register",
"name": "Total Import kWh",
"type": "electric_power",
"units": "kilowatts_hour"
},
{
"canRead": true,
"canWrite": false,
"code": "REG038",
"dataType": "float64",
"modbusAddress": "0x004A",
"modbusRegType": "input_register",
"name": "Total Export kWh",
"type": "electric_power",
"units": "kilowatts_hour"
},
{
"canRead": true,
"canWrite": false,
"code": "REG039",
"dataType": "float32",
"modbusAddress": "0x004C",
"modbusRegType": "input_register",
"name": "Total Import kVArh",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG040",
"dataType": "float32",
"modbusAddress": "0x004E",
"modbusRegType": "input_register",
"name": "Total Export kVArh",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG041",
"dataType": "float32",
"modbusAddress": "0x0050",
"modbusRegType": "input_register",
"name": "Total VAh",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG042",
"dataType": "float32",
"modbusAddress": "0x0052",
"modbusRegType": "input_register",
"name": "Ah",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG043",
"dataType": "float32",
"modbusAddress": "0x0054",
"modbusRegType": "input_register",
"name": "Total system power demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG044",
"dataType": "float32",
"modbusAddress": "0x0056",
"modbusRegType": "input_register",
"name": "Maximum total system power demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG051",
"dataType": "float32",
"modbusAddress": "0x0064",
"modbusRegType": "input_register",
"name": "Total system VA demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG052",
"dataType": "float32",
"modbusAddress": "0x0066",
"modbusRegType": "input_register",
"name": "Maximum total system VA demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG053",
"dataType": "float32",
"modbusAddress": "0x0068",
"modbusRegType": "input_register",
"name": "Neutral current demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG054",
"dataType": "float32",
"modbusAddress": "0x006A",
"modbusRegType": "input_register",
"name": "Maximum neutral current demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG101",
"dataType": "float32",
"modbusAddress": "0x00C8",
"modbusRegType": "input_register",
"name": "Line 1 to Line 2 volts",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG102",
"dataType": "float32",
"modbusAddress": "0x00CA",
"modbusRegType": "input_register",
"name": "Line 2 to Line 3 volts",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG103",
"dataType": "float32",
"modbusAddress": "0x00CC",
"modbusRegType": "input_register",
"name": "Line 3 to Line 1 volts",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG104",
"dataType": "float32",
"modbusAddress": "0x00CE",
"modbusRegType": "input_register",
"name": "Average line to line volts",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG113",
"dataType": "float32",
"modbusAddress": "0x00E0",
"modbusRegType": "input_register",
"name": "Neutral current",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG118",
"dataType": "float32",
"modbusAddress": "0x00EA",
"modbusRegType": "input_register",
"name": "Phase 1 L/N volts THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG119",
"dataType": "float32",
"modbusAddress": "0x00EC",
"modbusRegType": "input_register",
"name": "Phase 2 L/N volts THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG120",
"dataType": "float32",
"modbusAddress": "0x00EE",
"modbusRegType": "input_register",
"name": "Phase 3 L/N volts THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG121",
"dataType": "float32",
"modbusAddress": "0x00F0",
"modbusRegType": "input_register",
"name": "Phase 1 Current THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG122",
"dataType": "float32",
"modbusAddress": "0x00F2",
"modbusRegType": "input_register",
"name": "Phase 2 Current THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG123",
"dataType": "float32",
"modbusAddress": "0x00F4",
"modbusRegType": "input_register",
"name": "Phase 3 Current THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG125",
"dataType": "float32",
"modbusAddress": "0x00F8",
"modbusRegType": "input_register",
"name": "Average line to neutral volts THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG126",
"dataType": "float32",
"modbusAddress": "0x00FA",
"modbusRegType": "input_register",
"name": "Average line current THD",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG130",
"dataType": "float32",
"modbusAddress": "0x0102",
"modbusRegType": "input_register",
"name": "Phase 1 current demand",
"type": "generic",
"units": "amps"
},
{
"canRead": true,
"canWrite": false,
"code": "REG131",
"dataType": "float32",
"modbusAddress": "0x0104",
"modbusRegType": "input_register",
"name": "Phase 2 current demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG132",
"dataType": "float32",
"modbusAddress": "0x0106",
"modbusRegType": "input_register",
"name": "Phase 3 current demand",
"type": "electric_power",
"units": "uds"
},
{
"canRead": true,
"canWrite": false,
"code": "REG133",
"dataType": "float32",
"modbusAddress": "0x0108",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Maximum phase 1 current demand",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG134",
"dataType": "float32",
"modbusAddress": "0x010A",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Maximum phase 2 current demand",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG135",
"dataType": "float32",
"modbusAddress": "0x010C",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Maximum phase 3 current demand",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG168",
"dataType": "float32",
"modbusAddress": "0x014E",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Line 1 to line 2 volts THD",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG169",
"dataType": "float32",
"modbusAddress": "0x0150",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Line 2 to line 3 volts THD",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG170",
"dataType": "float32",
"modbusAddress": "0x0152",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Line 3 to line 1 volts THD",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG171",
"dataType": "float32",
"modbusAddress": "0x0154",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Average line to line volts THD",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG172",
"dataType": "float32",
"modbusAddress": "0x0156",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Total kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG173",
"dataType": "float32",
"modbusAddress": "0x0158",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "Total kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG174",
"dataType": "float32",
"modbusAddress": "0x015A",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 import kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG175",
"dataType": "float32",
"modbusAddress": "0x015C",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 import kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG176",
"dataType": "float32",
"modbusAddress": "0x015E",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 import kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG177",
"dataType": "float32",
"modbusAddress": "0x0160",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 export kWh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG178",
"dataType": "float32",
"modbusAddress": "0x0162",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 export kWh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG179",
"dataType": "float32",
"modbusAddress": "0x0164",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 export kWh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG180",
"dataType": "float32",
"modbusAddress": "0x0166",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 total kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG181",
"dataType": "float32",
"modbusAddress": "0x0168",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 total kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG182",
"dataType": "float32",
"modbusAddress": "0x016A",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 total kwh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG183",
"dataType": "float32",
"modbusAddress": "0x016C",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 import kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG184",
"dataType": "float32",
"modbusAddress": "0x016E",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 import kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG185",
"dataType": "float32",
"modbusAddress": "0x0170",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 import kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG186",
"dataType": "float32",
"modbusAddress": "0x0172",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 export kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG187",
"dataType": "float32",
"modbusAddress": "0x0174",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 export kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG188",
"dataType": "float32",
"modbusAddress": "0x0176",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 export kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG189",
"dataType": "float32",
"modbusAddress": "0x0178",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L1 total kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG190",
"dataType": "float32",
"modbusAddress": "0x017A",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L2 total kvarh",
"type": "generic"
},
{
"canRead": true,
"canWrite": false,
"code": "REG191",
"dataType": "float32",
"modbusAddress": "0x017C",
"modbusMaskWriteFullAddress": true,
"modbusRegType": "input_register",
"name": "L3 total kvarh",
"type": "generic"
}
],
"virtualVariables": []
}
* Crompton is a registered trademark of TE Connectivity Ltd.
Privacy Overview
Adquio

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.