Configuration for Circutor © CVM-C10 Network Analyzer

This time we open a new section in which we will publish the configuration of different devices that will help you avoid having to do it manually, if you use this device you can now copy and paste the configuration that we leave below.

{
  "code": "Analizador",
  "disabled": false,
  "instance": "modbus_rs485_1",
  "modbusMaxLength": 40,
  "modbusSlave": "90",
  "modbusTimeout": 150,
  "pollInterval": 5000,
  "schemaVersion": 5,
  "type": "modbusrtu",
  "variables": [
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_fase_L1",
      "dataType": "float64",
      "modbusAddress": "0",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión Fase L1 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Corriente_L1",
      "dataType": "float64",
      "modbusAddress": "2",
      "modbusRegType": "input_register",
      "name": "Analizador Intensidad L1 (A)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Activa_L1",
      "dataType": "float64",
      "modbusAddress": "4",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Activa L1 (KW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Inductiva_L1",
      "dataType": "float64",
      "modbusAddress": "6",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Inductiva L1 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Capacitiva_L1",
      "dataType": "float64",
      "modbusAddress": "8",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Capacitiva L1 (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Aparente_L1",
      "dataType": "float64",
      "modbusAddress": "10",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Aparente L1 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Factor_de_potencia_L1",
      "dataType": "float64",
      "modbusAddress": "12",
      "modbusRegType": "input_register",
      "name": "Analizador Factor de Potencia L1",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Cos_phi_L1",
      "dataType": "float64",
      "modbusAddress": "14",
      "modbusRegType": "input_register",
      "name": "Analizador Coseno de Fi L1",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_fase_L2",
      "dataType": "float64",
      "modbusAddress": "16",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión Fase L2 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Corriente_L2",
      "dataType": "float64",
      "modbusAddress": "18",
      "modbusRegType": "input_register",
      "name": "Analizador Intensidad L2 (A)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Activa_L2",
      "dataType": "float64",
      "modbusAddress": "20",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Activa L2 (KW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Inductiva_L2",
      "dataType": "float64",
      "modbusAddress": "22",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Inductiva L2 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Capacitiva_L2",
      "dataType": "float64",
      "modbusAddress": "24",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Capacitiva L2 (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Aparente_L2",
      "dataType": "float64",
      "modbusAddress": "26",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Aparente L2 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Factor_de_potencia_L2",
      "dataType": "float64",
      "modbusAddress": "28",
      "modbusRegType": "input_register",
      "name": "Analizador Factor de Potencia L2",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Cos_phi_L2",
      "dataType": "float64",
      "modbusAddress": "30",
      "modbusRegType": "input_register",
      "name": "Analizador Coseno de Fi L2",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_fase_L3",
      "dataType": "float64",
      "modbusAddress": "32",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión Fase L3 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Corriente_L3",
      "dataType": "float64",
      "modbusAddress": "34",
      "modbusRegType": "input_register",
      "name": "Analizador Intensidad L3 (A)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Activa_L3",
      "dataType": "float64",
      "modbusAddress": "36",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Activa L3 (KW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Inductiva_L3",
      "dataType": "float64",
      "modbusAddress": "38",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Inductiva L3 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Capacitiva_L3",
      "dataType": "float64",
      "modbusAddress": "40",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Capacitiva L3 (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Aparente_L3",
      "dataType": "float64",
      "modbusAddress": "42",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Aparente L3 (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Factor_de_potencia_L3",
      "dataType": "float64",
      "modbusAddress": "44",
      "modbusRegType": "input_register",
      "name": "Analizador Factor de Potencia L3",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Cos_phi_L3",
      "dataType": "float64",
      "modbusAddress": "46",
      "modbusRegType": "input_register",
      "name": "Analizador Coseno de Fi L3",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_Activa_trifasica",
      "dataType": "float64",
      "modbusAddress": "48",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Activa Trifásica (kW)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_inductiva_trifasica",
      "dataType": "float64",
      "modbusAddress": "50",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Inductiva Trifásica (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_capacitiva_trifasica",
      "dataType": "float64",
      "modbusAddress": "52",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Capacitiva Trifásica (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Potencia_aparente_trifasica",
      "dataType": "float64",
      "modbusAddress": "54",
      "modbusRegType": "input_register",
      "name": "Analizador Potencia Aparente Trifásica (kVar)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Factor_de_potencia_trifasica",
      "dataType": "float64",
      "modbusAddress": "56",
      "modbusRegType": "input_register",
      "name": "Analizador Factor de Potencia Trifásico",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Cos_phi_trifasico",
      "dataType": "float64",
      "modbusAddress": "58",
      "modbusRegType": "input_register",
      "name": "Analizador Coseno de Fi Trifásico",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Frecuencia_L1",
      "dataType": "float64",
      "modbusAddress": "60",
      "modbusRegType": "input_register",
      "name": "Analizador Frecuencia L1",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(100)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_L1_L2",
      "dataType": "float64",
      "modbusAddress": "62",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión L1/L2 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_L2_L3",
      "dataType": "float64",
      "modbusAddress": "64",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión L2/L3 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Tension_L3_L1",
      "dataType": "float64",
      "modbusAddress": "66",
      "modbusRegType": "input_register",
      "name": "Analizador Tensión L3/L1 (V)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Corriente_Neutro_N",
      "dataType": "float64",
      "modbusAddress": "68",
      "modbusRegType": "input_register",
      "name": "Analizador Intensidad Neutro (A)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(1000)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_tension_L1",
      "dataType": "float64",
      "modbusAddress": "70",
      "modbusRegType": "input_register",
      "name": "Analizador THD Tensión L1 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_tension_L2",
      "dataType": "float64",
      "modbusAddress": "72",
      "modbusRegType": "input_register",
      "name": "Analizador THD Tensión L2 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_tension_L3",
      "dataType": "float64",
      "modbusAddress": "74",
      "modbusRegType": "input_register",
      "name": "Analizador THD Tensión L3 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_Corriente_L1",
      "dataType": "float64",
      "modbusAddress": "76",
      "modbusRegType": "input_register",
      "name": "Analizador THD Intensidad L1 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_Corriente_L2",
      "dataType": "float64",
      "modbusAddress": "78",
      "modbusRegType": "input_register",
      "name": "Analizador THD Intensidad L2 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Porcentaje_THD_Corriente_L3",
      "dataType": "float64",
      "modbusAddress": "80",
      "modbusRegType": "input_register",
      "name": "Analizador THD Intensidad L3 (%)",
      "type": "generic",
      "valueConverters": [
        "cast(int32, float64)",
        "divide(10)"
      ]
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Energia_activa_kW",
      "dataType": "int32",
      "modbusAddress": "220",
      "modbusRegType": "input_register",
      "name": "Analizador Energía Activa (kWh)",
      "type": "generic",
      "valueConverters": []
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Energia_reactiva_inductiva_kvarhL",
      "dataType": "int32",
      "modbusAddress": "224",
      "modbusRegType": "input_register",
      "name": "Analizador Energía Reactiva Inductiva (kVarh)",
      "type": "generic",
      "valueConverters": []
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Energia_reactiva_capacitiva_kvarhC",
      "dataType": "int32",
      "modbusAddress": "228",
      "modbusRegType": "input_register",
      "name": "Analizador Energía Reactiva Capacitiva (kVarh)",
      "type": "generic",
      "valueConverters": []
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Energia_aparente_kVAh",
      "dataType": "int32",
      "modbusAddress": "232",
      "modbusRegType": "input_register",
      "name": "Analizador Energía Aparente (kVar)",
      "type": "generic",
      "valueConverters": []
    },
    {
      "canRead": true,
      "canWrite": false,
      "code": "Estado_potencia",
      "dataType": "uint16",
      "modbusAddress": "0x7d1",
      "modbusRegType": "holding_register",
      "type": "generic"
    }
  ],
  "virtualVariables": []
}
* Circutor is a registered trademark of CIRCUTOR, SA

Related Posts

Leave a Reply