As an expansion module
Connect the RS-485 slave port to an Adquio controller or another compatible Modbus RTU master. The controller reads the inputs and sends commands to the outputs.
Expansions and modules
Bring inputs and outputs together in a Modbus RTU expansion module. Adapt signal acquisition and control commands to each installation zone.

INPUTS, OUTPUTS AND MACHINE CONTROL
Connect sensors, PT1000 probes, relays and analogue and digital signals for heat exchangers, chillers, evaporator and condenser units, air handling units and other equipment.
Adquio Multi IOs combines inputs and outputs with Modbus RTU communication, simplifying machine integration and centralising its signals.

Connect the RS-485 slave port to an Adquio controller or another compatible Modbus RTU master. The controller reads the inputs and sends commands to the outputs.
For manufacturers and dedicated applications, custom programming can run the machine without a separate programmable controller. A compatible screen or thermostat can connect to the master port for local setpoints, status and manual control. This mode requires a project assessment and specific programming.


| Supply voltage | 24 V DC |
|---|---|
| Consumption | 130 mA |
| Maximum supported voltage | 28 V DC |
| Start-up peak | 150 mA |
| Slave port | 1 · RS-485 · Modbus RTU |
|---|---|
| Master port | 1 · RS-485 · Modbus RTU |
| Communication speed | 9600–19200 bps |
| Address | Microswitches |
| Configurable inputs | 8 · AI/DI |
|---|---|
| Analogue ranges | 0–10 V / 0–24 V |
| Digital logic 1 | > 4.7 V |
| Resolution | 12 bits |
| 4–20 mA inputs | Requires the DIN-rail converter |
| Temperature inputs | 4 · PT1000 |
|---|---|
| Resolution | 15 bits |
| Adjustment | Software-adjustable |
| Dry contacts | 5 |
|---|---|
| Current per contact | 10 A |
| Contact voltage | 250 V AC |
| Durability | More than 100,000 actuations |
| Outputs | 4 · 24 V · power transistors |
|---|---|
| Maximum load | 2 A |
| Outputs | 4 · 0–10 V |
|---|---|
| Resolution | 12 bits |
| Maximum load | 10 mA |
| Mounting | Horizontal · DIN 35 mm |
|---|---|
| Protection | IP20 |
| Operating temperature | 0–60 °C |
| Storage and transport | −40–70 °C |
| Relative humidity | ≤ 95% · non-condensing |
| Status LEDs | 3 · Power, Online, Error |
| Safety and health | EN ISO 13849-1: 2015 EN ISO 13849-2: 2012 EN 62061: 2005 + A1: 2013 + A2: 2015 EN 60950-1: 2006 EN 62311: 2008 |
|---|---|
| EMC | EN 61000-6-4: 2007 + A1: 2011 EN 61000-6-2: 2005 ETSI EN 301 489-1 v2.2.0 ETSI EN 301 489-17 v3.2.0 |
| RoHS | EN 50581: 2012 |
Measurements and status travel to the controller; commands return to the outputs through Modbus RTU.
Connect probes, sensors, relays and actuators to the appropriate inputs and outputs.

The module collects measurements and states, and switches or regulates the connected outputs.
Use a compatible Modbus RTU master, such as Adquio Mini, to coordinate logic, schedules and other building systems.
Use the controller’s variables for control interfaces, supervision and historical data analysis.
Plan your integration with our engineering team and find the right solution for your installation.