Controllers

Adquio Mini

Connect equipment to four RS-485 ports, gather its variables over Ethernet and control a zone or participate in a distributed architecture.

Adquio Mini

THE NEW STANDARD

Adquio Mini

Adquio Mini is a compact controller and data collector with four RS-485 ports and Ethernet. It integrates equipment over Modbus RTU, BACnet MS/TP over RS-485 and BACnet/IP over Ethernet, brings together variables from different platforms and participates in distributed control between Adquio controllers. It can also publish data over Modbus, BACnet or REST API, depending on the configured integration.

When to choose Adquio Mini

A compact integration point for collecting data, connecting protocols and controlling an installation zone.

01

Collect field data

Connect compatible Modbus RTU or BACnet MS/TP equipment to its four RS-485 ports. Check compatibility and bus settings for each device.

02

Distribute control

Use it as a zone controller or as a data collector in a multi-controller Adquio architecture. Shared variables help coordinate the installation.

03

Put information to work

Bring variables into your chosen monitoring environment. Adquio SCADA Server provides a local operating interface, while Adquio Analytics adds dashboards and historical analysis.

CONNECTIONS

adquio mini

Front connectors and top indicators

  1. 4 protected 485 ports.
  2. Error indicator.
  3. On with internet access, flashes when the WiFi access point is activated.
  4. On normal operation.
mini1-min
mini2-min

Rear connectors

  1. 24V DC power supply.
  2. 100Mb / s WAN network port.
  3. MMC 16Gb.

Tech Specs

Energy

Power supply
24VDC

Power

Processor
Quad-core ARM® Cortex™-A7

RAM
512Mb DDR3

Connectivity

Ethernet WAN Ports
1 (10/100 Mb/s)

WiFi
Hotspot Configuration
Ports 485
4 (Compatible with Modbus RTU and BACnet MS/TP up to 115200bps)
Storage

MMC

16 GB

Control

Indicator LEDs
2; Power and Online

Certifications

Safety and Health

EN ISO 13849-1: 2015

EN ISO 13849-2: 2012

EN 62061: 2005 + A1: 2013 + A2: 2015

EN 60950-1: 2006

EN 62311: 2008

EMC

EN 61000-6-4: 2007 + A1: 2011

EN 61000-6-2: 2005

ETSI EN 301 489-1 v2.2.0

ETSI EN 301 489-17 v3.2.0

RoHS

EN 50581:2012

Electrical, mechanical and environmental specifications

Power supply and consumption

Power connectorRemovable 2-contact terminal block · 5.08 mm pitch.
Maximum supported voltage28 V DC
Reverse voltage protectionYes
Nominal protection fuseUp to 3 A
Current from a 24 V supply90–150 mA
Maximum current150 mA
Maximum start-up current150 mA

Dimensions, mounting and environmental conditions

Body dimensions70 × 90 × 56 mm · total height including connections: 106 mm.
MountingHorizontal; 35 mm DIN rail to DIN EN 50022, 7.5 or 15 mm depth; alternatively with 4 mm screws.
Tightening torque1.2 Nm
HousingABS UL-94-HB · dark grey
Ingress protectionIP20
Operating temperature0 °C to +60 °C · mounted horizontally on a DIN rail.
Storage and transport−40 °C to +70 °C
HumidityMaximum 95%, non-condensing.
Operating air pressure> 800 hPa · altitude < 2,000 m.
Storage air pressure> 600 hPa · altitude < 3,500 m.

Radio standards

  • EN 300 328 V2.1.1
  • EN 301 893 V2.1.1

FROM DEVICE DATA TO BUILDING MANAGEMENT

One controller. More ways to use your data.

Adquio Mini connects devices, brings together variables and runs the configured control logic. Use that information in screens, SCADA, dashboards and building management platforms according to your project’s needs.

Choose the tools each user needs. Data exchange and available actions depend on the interfaces, variables and permissions configured for the project; these platforms complement the controller’s operation.

Protocols/Integrations

Use BACnet/IP over Ethernet or BACnet MS/TP over the controller’s RS-485 ports, according to the device connection.

mini0-min

Connect your project with the Adquio ecosystem.

Plan your integration with our engineering team and find the right solution for your installation.

Privacy Overview
Adquio

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.

Strictly Necessary Cookies

Strictly Necessary Cookie should be enabled at all times so that we can save your preferences for cookie settings.

Analytics

These cookies measure visits and contact enquiries using Google Analytics and Clientify analytics. They are only enabled if you accept them.

Advertising

These cookies enable Google advertising features and measure their performance. They are only enabled if you accept them.