Room and zone control
Adquio screens and interfaces
Show states and trends, adjust setpoints and activate scenes through an interface tailored to each space.
Explore the solutionControllers
Connect equipment to four RS-485 ports, gather its variables over Ethernet and control a zone or participate in a distributed architecture.

THE NEW STANDARD
Adquio Mini is a compact controller and data collector with four RS-485 ports and Ethernet. It integrates equipment over Modbus RTU, BACnet MS/TP over RS-485 and BACnet/IP over Ethernet, brings together variables from different platforms and participates in distributed control between Adquio controllers. It can also publish data over Modbus, BACnet or REST API, depending on the configured integration.
A compact integration point for collecting data, connecting protocols and controlling an installation zone.
01
Connect compatible Modbus RTU or BACnet MS/TP equipment to its four RS-485 ports. Check compatibility and bus settings for each device.
02
Use it as a zone controller or as a data collector in a multi-controller Adquio architecture. Shared variables help coordinate the installation.
03
Bring variables into your chosen monitoring environment. Adquio SCADA Server provides a local operating interface, while Adquio Analytics adds dashboards and historical analysis.
adquio mini
| Power supply | 24VDC |
| Processor | Quad-core ARM® Cortex™-A7 |
| RAM | 512Mb DDR3 |
| Ethernet WAN Ports | 1 (10/100 Mb/s) |
| WiFi | Hotspot Configuration |
| Ports 485 | 4 (Compatible with Modbus RTU and BACnet MS/TP up to 115200bps) |
MMC
16 GB
| Indicator LEDs | 2; Power and Online |
Safety and Health
EN ISO 13849-1: 2015
EN ISO 13849-2: 2012
EN 62061: 2005 + A1: 2013 + A2: 2015
EN 60950-1: 2006
EN 62311: 2008
EMC
EN 61000-6-4: 2007 + A1: 2011
EN 61000-6-2: 2005
ETSI EN 301 489-1 v2.2.0
ETSI EN 301 489-17 v3.2.0
RoHS
EN 50581:2012
| Power connector | Removable 2-contact terminal block · 5.08 mm pitch. |
| Maximum supported voltage | 28 V DC |
| Reverse voltage protection | Yes |
| Nominal protection fuse | Up to 3 A |
| Current from a 24 V supply | 90–150 mA |
| Maximum current | 150 mA |
| Maximum start-up current | 150 mA |
| Body dimensions | 70 × 90 × 56 mm · total height including connections: 106 mm. |
| Mounting | Horizontal; 35 mm DIN rail to DIN EN 50022, 7.5 or 15 mm depth; alternatively with 4 mm screws. |
| Tightening torque | 1.2 Nm |
| Housing | ABS UL-94-HB · dark grey |
| Ingress protection | IP20 |
| Operating temperature | 0 °C to +60 °C · mounted horizontally on a DIN rail. |
| Storage and transport | −40 °C to +70 °C |
| Humidity | Maximum 95%, non-condensing. |
| Operating air pressure | > 800 hPa · altitude < 2,000 m. |
| Storage air pressure | > 600 hPa · altitude < 3,500 m. |
FROM DEVICE DATA TO BUILDING MANAGEMENT
Adquio Mini connects devices, brings together variables and runs the configured control logic. Use that information in screens, SCADA, dashboards and building management platforms according to your project’s needs.

Room and zone control
Show states and trends, adjust setpoints and activate scenes through an interface tailored to each space.
Explore the solution
Local supervision and control
Display the installation on floor plans, review states and alarms and operate devices through the local server.
Explore the solution
Cloud supervision and control
Access supervision and control interfaces through a cloud-hosted platform with authorised access.
Explore the solution
Dashboards and analysis
Turn recorded variables into charts and indicators. Analyse energy use, temperatures and changes over time.
Explore the solution
Multi-site management
Bring together data from multiple sites, apply advanced formulas and compare indicators such as energy use per square metre.
Explore the solution
Infrastructure health
Organise devices by building and zone, check their status and locate issues to support maintenance.
Explore the solutionChoose the tools each user needs. Data exchange and available actions depend on the interfaces, variables and permissions configured for the project; these platforms complement the controller’s operation.
Plan your integration with our engineering team and find the right solution for your installation.